Schneider

TM3AI8 | Schneider 8-Channel Analog Input Module

  • Model TM3AI8
  • Condition In Stock
4.6/5 (16 reviews)
$224.00 Indicative price · request a quote for availability

Schneider TM3AI8 analog input module: 8 configurable channels, 12-bit resolution, 1500 V AC isolation. Cut wiring costs and protect your Modicon PLC investment.

Product Description

Why the TM3AI8 Belongs in Your Spare Parts Strategy

Unplanned downtime on a Modicon M221, M241, M251, or M262 line often traces back to one failed analog input module. The Schneider TM3AI8 solves that problem directly. It is an 8-channel analog input expansion module from the Modicon TM3 series, and it converts voltage or current field signals into digital values your controller can use. Each channel is software configurable, so one module covers four signal ranges instead of forcing you to stock four different part numbers. That single fact reduces inventory carrying costs and simplifies your spare parts budget.

Figure 1: Front view of the Schneider TM3AI8 industrial automation component showing its physical design and enclosure.

Technical Specifications That Drive Real Savings

Eight Channels, One Module

The TM3AI8 provides 8 input channels. A single module replaces two 4-channel units, which saves panel space and reduces the number of spare modules you must keep on the shelf. Fewer stocked parts mean lower capital tied up in inventory.

Flexible Signal Ranges

Each channel accepts 0-10 Vdc, ±10 Vdc, 0-20 mA, or 4-20 mA. You configure the range in software per channel. This flexibility means you can standardize on one module type across multiple machines, which lowers procurement complexity and training costs for your maintenance team.

12-Bit Resolution and Accuracy

The module delivers 12-bit resolution (11 bits plus sign for bipolar ranges). Accuracy is ±0.1% of full scale at 25 °C, with ±1% of full scale over the full temperature range. For process control, that level of accuracy reduces measurement error, which protects product quality and avoids costly batch rejects.

Isolation Protects Your Investment

Isolation is 1500 V AC between input and supply, and 500 V AC between input and internal logic. This barrier limits fault propagation from field wiring into the controller backplane. Avoiding a single damaged PLC rack can save thousands in replacement cost and lost production.

Fast Response Time

Conversion takes 1 ms plus 1 ms per channel plus one controller cycle time. Sampling is 1 ms per channel. Fast sampling supports tighter control loops, which improves throughput on high-speed packaging and assembly equipment.

Where the TM3AI8 Earns Its Place

Process Skid Monitoring

A skid builder running a Modicon M241 can use the TM3AI8 to read pressure, flow, and level transmitters on 4-20 mA loops. The 12-bit resolution captures small process changes, so operators catch drift before it becomes scrap.

Replacement and Upgrade Path

When an older analog card fails, the TM3AI8 offers a clean upgrade path for M221, M241, M251, and M262 platforms. Because the module is active in the lifecycle, you avoid the cost of redesigning your control panel around an obsolete part.

Utility and Building Automation

Voltage inputs at 0-10 Vdc suit damper position and temperature sensors. The IP20 rating fits inside a clean cabinet, and the 0…+55 °C operating range covers most plant rooms without extra cooling.

Figure 2: Technical layout and connection details for the Schneider TM3AI8 industrial automation component.

Installation and Setup Notes

Mount the module on the TM3 bus and secure it in the enclosure. Wiring uses a removable screw terminal block with 3.81 mm pitch, which speeds field termination and lets you pre-wire harnesses. Supply voltage is 24 Vdc through the TM3 bus. Bus current draw is 50 mA at 5 V DC at full load and 40 mA at 24 V DC. Plan your power budget around those figures to avoid overloading the bus.

Maintenance and Reliability

Inspect terminal connections periodically for looseness and corrosion. Verify channel and module diagnostics during routine checks, since the module reports channel status, module status, and bus status. Keep the cabinet within the 0…+55 °C operating range and respect the IP20 rating by avoiding condensation and dust ingress. Storage temperature is -25…+70 °C, so spare units tolerate normal warehouse conditions. The module weighs 0.115 kg and measures 90 × 23.6 × 70 mm, so it stores easily in a compact spares cabinet.

Compatibility and Selection Checklist

Confirm your controller is a Modicon M221, M241, M251, or M262 before ordering. Verify the signal type each field device produces, and confirm the 3.81 mm pitch terminal block matches your wiring plan. Check that your 24 Vdc supply and bus current budget support the module. Please verify current lifecycle status and availability with SpareTechPLC before ordering.

Frequently Asked Questions

How many analog inputs does the TM3AI8 provide?

It provides 8 analog input channels, each configurable in software for voltage or current operation.

Which signal ranges does the TM3AI8 support?

The module supports 0-10 Vdc, ±10 Vdc, 0-20 mA, and 4-20 mA ranges.

What is the resolution of the TM3AI8?

Resolution is 12 bits, which is 11 bits plus sign for bipolar ranges.

Which Schneider controllers work with this module?

It is compatible with Modicon M221, M241, M251, and M262 platforms.

What isolation does the TM3AI8 offer?

Isolation is 1500 V AC between input and supply, and 500 V AC between input and internal logic.

Specifications

Model / No. TM3AI8
Brand Schneider
Condition In Stock
Origin US
Warranty 12 Month
Price $224.00

Additional Information

Schneider Electric TM3AI8 analog input module from the Modicon TM3 series. 8 software-configurable channels, 12-bit resolution, 1500 V AC isolation, 24 Vdc supply via TM3 bus. Compatible with Modicon M221, M241, M251, and M262. Active lifecycle. Verify availability with SpareTechPLC.

Shipping & Returns

Shipping Port
Xiamen

Downloads

Download Instruction Manual (TM3AI8.pdf)

Latest News

View All News