Schneider

OTB1C0DM9LP | Schneider CANopen I/O Distributed Module

  • Model OTB1C0DM9LP
  • Condition In Stock
4.6/5 (16 reviews)
$218.00 Indicative price · request a quote for availability

Schneider OTB1C0DM9LP CANopen I/O distributed module with 12 inputs, 2 solid-state and 6 relay outputs. Ideal for distributed control.

Product Description

OTB1C0DM9LP Overview

When you need reliable distributed I/O for a CANopen network, the Schneider OTB1C0DM9LP delivers. This Modicon OTB I/O distributed module combines discrete inputs and outputs in one compact unit. It supports CANopen S20 with DS 401 V2.1 profile and uses CSMA/MA multimaster with priority access. The integrated SUB-D 9 connection handles transmission speeds from 10 kbit/s to 1 Mbit/s over two twisted shielded pairs. This makes it a flexible building block for machine builders and system integrators.

Figure 1: Front view of the Schneider OTB1C0DM9LP industrial automation component showing its physical design and enclosure.

Key Technical Specifications

| Parameter | Value |

|————|——-|

| Discrete inputs | 12 (EN/IEC 61131 type 1) |

| Input logic | Sink or source (NPN/PNP) |

| Input voltage | 24 VDC (20.4…26.4 V) |

| Discrete outputs | 2 solid-state PNP (source), 6 relay |

| Output voltage | 24 VDC solid-state; 30 VDC / 240 VAC relay |

| Output current | 300 mA solid-state; 2000 mA relay |

| Bus length | 0…1000 m at 50 kbit/s (tap-off 0…120 m) |

| Supply voltage | 24 VDC (20.4…26.2 V) |

| Power consumption | 19 W |

| Product weight | 0.195 kg |

| Protection | IP20 |

Industry Applications

The OTB1C0DM9LP fits perfectly into material handling, packaging, and process control systems. Its 12 discrete inputs accept both sink and source signals, so you can connect a variety of sensors and switches. The two solid-state PNP outputs switch fast (5 µs response) for high-speed actuation, while the six relay outputs handle higher currents (up to 2 A) for contactors or small motors. Because it supports up to 63 slaves on the bus, you can expand your network without adding extra controllers.

Figure 2: Technical layout and connection details for the Schneider OTB1C0DM9LP industrial automation component.

Installation & Setup

Mount the module on a 35 mm symmetrical DIN rail using the integrated clips, or panel-mount with an optional fixing kit. The removable screw terminal block simplifies wiring. Connect the CANopen bus via the SUB-D 9 connector, ensuring proper termination and shielding. For bus lengths up to 1000 m at 50 kbit/s, keep tap-off lengths under 120 m. Always verify the supply voltage stays within 20.4…26.2 VDC to avoid operational issues.

Maintenance & Reliability

The OTB1C0DM9LP is built for long service life. Relay outputs are rated for 500,000 cycles under various loads (AC-1, AC-14, AC-15, DC-1, DC-13). Solid-state outputs have no moving parts, reducing wear. The module withstands vibration up to 1 gn (57…150 Hz) and shock up to 15 gn for 11 ms. Operate within 0…55 °C ambient temperature and 30…95 % humidity (non-condensing) for best reliability. Periodically check connections and bus cabling to prevent communication errors.

Compatibility & Integration

The OTB1C0DM9LP is designed for CANopen networks. It supports up to 63 slaves and can be daisy-chained or connected via tap junctions. You can add up to 7 I/O expansion modules, increasing your I/O count up to 244 points with HE10 connector modules. This makes it easy to scale your system as needs grow. The module is CSA and UL 508 certified, and carries CE marking.

Selection Guide & Purchasing Advice

Before ordering, verify your bus speed and cable length requirements. The OTB1C0DM9LP supports speeds from 10 kbit/s to 1 Mbit/s, with corresponding bus length limits (e.g., 1000 m at 50 kbit/s). Check your output needs: solid-state for fast switching or relay for higher current. SpareTechPLC offers genuine Schneider modules with fast shipping and expert support. Contact us to confirm availability and lifecycle status.

Troubleshooting & Common Issues

If the module does not communicate, check the CANopen bus termination and cable shielding. Ensure the supply voltage is within 20.4…26.2 VDC. If outputs fail, verify the load current does not exceed 2 A for relays or 300 mA for solid-state outputs. For input issues, confirm the input voltage is 24 VDC and within 20.4…26.4 V. Use the status LEDs (PWR, RUN, ERR) to diagnose faults. The green PWR LED indicates power; the red ERR LED signals bus errors.

Frequently Asked Questions

Q1: What is the maximum bus length for the OTB1C0DM9LP?

At 50 kbit/s, the bus length can reach 1000 m with tap-off lengths up to 120 m. For higher speeds, the length decreases (e.g., 250 m at 250 kbit/s).

Q2: Can I use both solid-state and relay outputs simultaneously?

Yes. The module has two solid-state PNP outputs (Q0…Q1) and six relay outputs (Q2…Q7). They operate independently, giving you flexibility.

Q3: What is the input current consumption?

Each input draws 5 mA (for I0…I1 and I6…I7) or 7 mA (for I2…I5 and I8…I11). This is within typical sensor capabilities.

Q4: Does the module support both NPN and PNP sensors?

Yes. The discrete inputs accept both sink (NPN) and source (PNP) logic, making it compatible with most sensors.

Q5: What is the response time for solid-state outputs?

Solid-state outputs switch in 5 µs (both state 0 and state 1), ideal for high-speed applications. Relay outputs have a 300 µs response time.

Specifications

Model / No. OTB1C0DM9LP
Brand Schneider
Condition In Stock
Origin US
Warranty 12 Month
Price $218.00

Additional Information

OTB1C0DM9LP
I/O distributed module OTB - CANopen bus -
0..1000 m

Main
Range of product Modicon OTB
Product or component type I/O distributed module
Integrated connection type CANopen bus SUB-D 9, transmission mode: 2 twisted shielded pairsat 10 kbit/s...1 Mbit/s
Bus type CANopen S20, profile: DS 401 V2.1, method of access: CSMA/MA multimaster with priority
conforming to DR303-2
CANopen S20, profile: DS 401 V2.1, method of access: CSMA/MA multimaster with priority
conforming to DS301 V4.02
Discrete input number 12 conforming to EN/IEC 61131 type 1
Discrete input logic Sink or source
Discrete input current 5 mA for I0...I1
5 mA for I6...I7
7 mA for I2...I5
7 mA for I8...I11
Discrete output number 2 solid state PNP for Q0...Q1 output logic: source
6 relay for Q2...Q7
Discrete output current 2000 mA relay
300 mA solid state
Complementary
Topology Devices linked by daisy-chaining or tap junctions
Number of slave 0...63
Bus length 0...100 m tap-off length: 0...10 m, 500 kbit/s
0...1000 m tap-off length: 0...120 m, 50 kbit/s
0...250 m tap-off length: 0...10 m, 250 kbit/s
0...2500 m tap-off length: 0...300 m, 20 kbit/s
0...40 m tap-off length: 0...6 m, 800 kbit/s
0...500 m tap-off length: 0...10 m, 125 kbit/s
0...5000 m tap-off length: 0...600 m, 10 kbit/s
0...20 m, 1 Mbit/s
Number of devices per segment 0...16, length of segment 0...205 m
0...32, length of segment 0...185 m
0...64, length of segment 0...160 m

Discrete input voltage 24 V
Discrete input voltage type DC
Discrete input type NPN or PNP
Input voltage limits 20.4...26.4 V
Electronic filtering time 0.035 ms for I0...I1 at state 1
0.035 ms for I6...I7 at state 1
0.04 ms for I2...I5 at state 1
0.04 ms for I8...I11 at state 1
0.045 ms for I0...I1 at state 0
0.045 ms for I6...I7 at state 0
0.15 ms for I2...I5 at state 0
0.15 ms for I8...I11 at state 0
Configurable filtering time 0 ms
12 ms
3 ms
Input impedance 3.4 kOhm for I2...I5
3.4 kOhm for I8...I11
5.7 kOhm for I0...I1
5.7 kOhm for I6...I7
Discrete output voltage 24 V DC solid state
240 V AC relay
30 V DC relay
Output voltage limits 20.4...28.8 V solid state
Output current limits 360 mA solid state
Current per output common 8 A relay
= 0.1 mA
Contact bounce time <= 1 ms for relay Leakage current <= 0.1 mA at state 0 for solid state Drop-out voltage <= 1 V at state 1 Insulation between channels and internal logic 1500 Vrms for 1 minute for relay output 500 Vrms for 1 minute for input circuit 500 Vrms for 1 minute for solid state output Insulation between channels None Contact resistance <= 30 mOhm Electrical durability 500000 cycles AC-1 with 500 VA load for relay output 500000 cycles AC-14 with 250 VA load for relay output 500000 cycles AC-15 with 200 VA load for relay output 500000 cycles DC-1 with 60 W load for relay output 500000 cycles DC-13 with 30 W load for relay output Supply circuit type DC [Us] rated supply voltage 24 V Supply voltage limits 20.4...26.2 V Input current <= 700 mA at 26.2 V for supply circuit Inrush current <= 1 A for solid state output = 10 mOhm between I/O and earth terminals

>= 10 mOhm between power supply and earth
I/O connection Removable screw terminal block
Number of common point 1 for relay output (1 NO)
1 for relay output (2 NO)
1 for relay output (3 NO)
1 for input
1 for solid state output
Counting input number 2
Counting capacity 32 bits
Counting frequency 20000 Hz
5000 Hz
Pulse generator number 2
Pulse generator frequency 7 kHz
Pulse generator function RPLS pulse generator output
RPWM pulse width modulation
Marking CE
Fixing mode By clips on 35 mm symmetrical DIN rail
By screws on panel with fixing kit
By screws on solid plate with fixing kit
Status LED 1 LED per channel, green for I/O
1 LED, green for PWR
1 LED, green for RUN
1 LED, red for ERR
Product weight 0.195 kg
Environment
IP degree of protection IP20
Immunity to microbreaks 10 ms for supply circuit
Dielectric strength 500 V between I/O and earth terminals
500 V between power supply and earth
Standards CSA
EN 61131-2
IEC 61131-2
UL 508
CSA C22.2 No 213 Class I Division 2 Group A
CSA C22.2 No 213 Class I Division 2 Group B
CSA C22.2 No 213 Class I Division 2 Group C
CSA C22.2 No 213 Class I Division 2 Group D
Product certifications CULus
Ambient air temperature for operation 0...55 °C
Ambient air temperature for storage -25...70 °C
Relative humidity 30...95 % without condensation
Pollution degree 2 conforming to EN 60664
2 conforming to IEC 60664
Operating altitude 0...2000 m
Storage altitude 0...3000 m
Vibration resistance 0.075 mm (f = 10...57 Hz) on 35 mm symmetrical DIN rail
1 gn (f = 57...150 Hz) on 35 mm symmetrical DIN rail
Shock resistance 15 gn for 11 ms conforming to EN 61131
15 gn for 11 ms conforming to IEC 61131
Resistance to electrostatic discharge 4 kV in contact conforming to IEC 61000-4-2
8 kV in air conforming to EN 61000-4-2
8 kV in air conforming to IEC 61000-4-2
4 kV in contact conforming to EN 61000-4-2
Resistance to radiated fields 10 V/m, 80000000...2000000000 Hz conforming to EN 61000-4-3
10 V/m, 80000000...2000000000 Hz conforming to IEC 61000-4-3
Resistance to fast transients 1 kV for 24 V solid state I/O conforming to IEC 61000-4-4
2 kV for 24 V supply conforming to IEC 61000-4-4

Shipping & Returns

Shipping Port
Xiamen
Shipping Details
Ships within 1-3 business days after payment via DHL / FedEx / UPS Express, or by sea/air freight for bulk orders. Tracking number is provided the same day the parcel leaves our warehouse.
Return Policy
30-day return for unused items in original packaging. All parts are covered by a 12-month warranty against defects; DOA units are replaced free of charge.

Downloads

Download Instruction Manual (Schneider_OTB1C0DM9LP_Service_Manual.pdf)

Latest News

View All News