When a Single Faulty Channel Shuts Down Your Line
An engineer at a packaging plant faced a familiar problem. One shorted output channel on a legacy SLC 500 rack tripped the entire module, halting production for hours. The fix came from a module designed to isolate faults instead of spreading them: the Allen-Bradley 1746-OBP16.
This SLC 500 Digital DC Output Module delivers Sixteen (16) sourcing channels with an output voltage range of 20.4-26.4 Volts DC. Each channel carries its own electronic fuse protection, so a single fault does not take down the rest of the rack.

What Makes the 1746-OBP16 Different
Most output modules fail as a unit. The 1746-OBP16 fails as a channel. Its integrated fuse protects against short-circuit and overload current, and the front-panel E-FUSE LED illuminates when a fault occurs. Other channels keep operating without interruption.
This channel-level isolation changes how maintenance teams respond. Instead of replacing an entire module, technicians correct the fault, cycle system power, and the module resets automatically. That automatic fault recovery behavior must be factored into the system’s fail-safe operating conditions.
Technical Specifications That Matter
Output Capacity
The module provides Sixteen (16) outputs at 1.5 or 1 amps per channel, with a total module current of 6.4 amps. This makes it suitable for high-current applications where standard output cards fall short.
Response Speed
Step response is 60 milliseconds in and 2.5 milliseconds out. The fast turn-off time supports applications requiring quick de-energization.
Backplane Load
The module draws 250 milliamps from the 5 Volt backplane, a modest load that leaves headroom in most SLC 500 chassis configurations.
Fuse Protection
The integrated fuse maintains UL/CSA rating. Compatible replacements are Littelfuse #322010,10A or #332010,10A. Allen-Bradley’s fuse kit is catalog number 1746-F8, containing Five (5) fuses per kit. Replacing the fuse requires pulling the module from the chassis.

Where This Module Fits
High-Current Output Applications
Manufacturing lines driving solenoids, contactors, or indicator banks benefit from the 1.5 or 1 amp per-channel capacity. The sourcing configuration matches common 24VDC control architectures.
Legacy SLC 500 Retrofits
Plants maintaining existing SLC 500 infrastructure can drop this module into a single chassis slot without rewiring. It works in both fixed and modular style hardware.
Fault-Tolerant Control Panels
When one output failure cannot be allowed to stop the process, per-channel fusing keeps the remaining Fifteen (15) channels live while maintenance responds.
Installation and Setup
Install the 1746-OBP16 in any single slot of an SLC 500 chassis, whether fixed or modular. Use signal wires up to 2 mm sq. (14 AWG). Confirm the 5 Volt backplane can supply 250 milliamps to the module.
Before commissioning, verify the fail-safe behavior of your system. Automatic fault recovery means the module resumes output after power cycling, which may not suit every safety architecture.
Maintenance and Reliability
Inspect the E-FUSE LED during routine rounds. A lit LED signals a faulted channel requiring correction. When replacing fuses, use only Littelfuse #322010,10A or #332010,10A to preserve UL/CSA rating.
Keep spare fuse kits (1746-F8) on hand. The five-fuse kit covers multiple fault events without waiting on procurement, reducing mean time to repair.
Compatibility and Integration
The 1746-OBP16 belongs to the SLC 500 family and integrates with existing SLC 500 processors and chassis. It occupies one slot and requires no special configuration beyond standard output addressing.
Selection Checklist
Before ordering, confirm your application needs sourcing outputs, 24VDC nominal voltage, and per-channel fuse protection. Verify your chassis has an open slot and sufficient backplane capacity.
SpareTechPLC stocks the 1746-OBP16 and related fuse kits. Please verify current lifecycle status and availability with SpareTechPLC before ordering.
Frequently Asked Questions
Q: What happens when one channel faults?
A: The E-FUSE LED illuminates, that channel shuts down, and the other channels continue operating normally.
Q: How do I recover a faulted channel?
A: Correct the fault, remove system power, then reapply power. The module resets automatically.
Q: Which fuses are compatible?
A: Littelfuse #322010,10A or #332010,10A. The Allen-Bradley fuse kit is 1746-F8.
Q: What wire size should I use?
A: Signal wires up to 2 mm sq. (14 AWG).